Technical specification document defining performance ratings, standards compliance, construction requirements, submittal procedures, and quality assurance criteria for Model FSD-200 series combination fire smoke dampers under CSI Division 23 HVAC.
Document Type:
Product Specification Guide
Product Name:
Model FSD-200 Series Combination Fire Smoke Dampers
Manufacturer:
Greenheck India Private Limited
Address:
Off No. 541-542, Tower B3, Spaze I-Tech Park, Sector-49, Sohna Road, Gurgaon – 122018, Haryana, India
Facility Service Subgroup:
Division 23 HVAC (Previously Division 15)
Applicable Standards:
UL 555 (Seventh Edition); UL 555S (Fourth Edition); AMCA 500-D; AMCA 511; NFPA 80; NFPA 90A; NFPA 92A; NFPA 92B; NFPA 101; NFPA 105; International Building Code (IBC)
UL Listing:
R13317
Fire Resistance Rating:
1½ hours or 3 hours
Fire Closure Temperature Options:
165°F; 212°F; 350°F
Copyright Holder:
Greenheck India Private Limited
Intended Use:
Preparation of written product specifications under CSI MasterFormat Division 23
Subject:
Combination fire smoke dampers with steel 3-V blades
Price: 8 / 10 USD
The file will be delivered to the email address provided at checkout within 12 hours.
The file will be delivered to the email address provided at checkout within 12 hours.
Don’t have cryptocurrency yet?
You can still complete your purchase in a few minutes:- Buy Crypto in a trusted app (Coinbase, Kraken, Cash App or any similar service).
- In the app, tap Send.
- Select network, paste our wallet address.
- Send the exact amount shown above.
The final amount may vary slightly depending on the payment method.
The file will be sent to the email address provided at checkout within 24 hours.
The product description is provided for reference. Actual content and formatting may differ slightly.
Year:
2015
Region / City:
Kansas City, Missouri
Subject:
HVAC systems, dampers, air control devices
Document Type:
Product specification
Organization / Institution:
Ruskin Company
Author:
Ruskin Company
Target Audience:
Specifiers, engineers, and HVAC system designers
Period of validity:
Not specified
Approval Date:
Not specified
Date of amendments:
Not specified
Year:
2015
Region / City:
Kansas City, Missouri
Theme:
HVAC Systems
Document Type:
Product Specification
Organization / Institution:
Ruskin Company
Author:
Ruskin Company
Target Audience:
Specifiers, HVAC engineers
Period of Validity:
Not specified
Approval Date:
Not specified
Amendment Date:
Not specified
Note:
Year
Model:
CB-601
Product Name:
Backdraft Dampers
Division:
23 – Heating, Ventilation, and Air Conditioning (HVAC)
Section Number:
233313 (Previously 15820)
Type of Operation:
Gravity operated or actuator operated
Manufacturer:
United Enertech
Manufacturer Address:
3005 South Hickory Street, Chattanooga, TN 37407
Manufacturer Phone:
(423) 698-7715
Standards Referenced:
AMCA 500-D; AMCA 511
Maximum Velocity:
4000 fpm (20.4 m/s)
Temperature Range:
-40°F to 200°F (-40°C to 93°C)
Differential Pressure Rating:
4.0 in. wg. (99.6 kPa)
Leakage Rating:
12 cfm/ft² @ 1 in. wg.
Frame Material:
Extruded aluminum
Blade Material:
Extruded aluminum
Seal Material:
Extruded vinyl
Mounting Orientation:
Vertical or horizontal
Warranty Period:
5 years
Factory Testing:
Cycle tested for proper operation
Applicable Systems:
HVAC duct systems
Related Sections:
233100 – HVAC Ducts and Casings; 230913.13 – Actuators and Operators
Model:
FD-B Static Curtain Fire Dampers
Division:
23 – Heating, Ventilation, and Air Conditioning (HVAC)
Section Number:
233313 (Previously 15820)
Document Type:
Product Specification Guide
Manufacturer:
United Enertech
Manufacturer Address:
3005 South Hickory Street, Chattanooga, TN 37407
Applicable Standards:
UL 555; NFPA 90A; NFPA 90B; NFPA 101; AMCA 500-D; AMCA 511; IBC; CSFM
Fire Rating Options:
1½ hours; 3 hours
Release Temperature Options:
165 ºF (74 ºC); 212 ºF (100 ºC)
Mounting Orientation:
Vertical and/or Horizontal
Warranty Period:
5 years
Application:
Static HVAC duct penetrations through fire-resistance-rated barriers
Execution Requirements:
Examination, Installation, Handling, Delivery, Storage
Division:
23 – Heating, Ventilation, and Air Conditioning (HVAC)
Section:
233313 (Previously 15820)
Product Name:
Backdraft Dampers
Model:
CB-600
Manufacturer:
United Enertech
Manufacturer Address:
3005 South Hickory Street, Chattanooga, TN 37407
Standards Referenced:
Air Movement and Control Association (AMCA 500-D, AMCA 511)
Applicable Systems:
HVAC systems up to 2800 fpm (14.2 m/s)
Temperature Range:
-40°F to 200°F (-40°C to 93°C)
Maximum Velocity:
2800 fpm (14.2 m/s)
Differential Pressure Rating:
3.0 in. wg. (0.74 kPa)
Leakage Rating:
8.7 cfm/ft² @ 1 in. wg.
Construction Material:
Extruded aluminum frame and blades
Blade Operation:
Gravity operated or actuator operated
Mounting Orientation:
Vertical or horizontal (upblast or downblast)
Actuator Options:
Electric 24VAC, 120VAC, 230VAC with open or closed fail position
Warranty Period:
5 years
Testing Requirements:
Pressure drop and leakage ratings in accordance with AMCA 500-D
Quality Control:
Factory cycled prior to shipment
Year:
NA
Region / City:
NA
Topic:
Seismic engineering, high-rise buildings
Document Type:
Research project report
Institution:
NA
Author:
NA
Target Audience:
Engineers, researchers in structural and seismic engineering
Period of validity:
NA
Approval Date:
NA
Date of revisions:
NA
Context:
Research on seismic protection systems for high-rise buildings using LRB isolators and VE dampers.
Year:
2023
Region / City:
Chattanooga, TN
Topic:
Fire Dampers, HVAC Systems
Document Type:
Product Specification
Organization:
United Enertech
Author:
Not specified
Target Audience:
Engineers, Contractors
Effective Period:
Not specified
Approval Date:
Not specified
Amendment Date:
Not specified
Year:
2026
Region / City:
United States
Subject:
Smoke protection systems
Document Type:
Technical specification
Organization / Institution:
Not specified
Author:
Not specified
Target Audience:
Contractors, engineers, installers
Effective Period:
Not specified
Approval Date:
Not specified
Amendment Date:
Not specified
Context Description:
Technical specification for the installation and maintenance of fixed draft-protective curtain assemblies for smoke containment in construction projects.
Year of Issue:
Not specified
Company:
International Fireproof Technology, Inc.
Address:
17528 Von Karman Ave., Irvine, CA 92614, USA
Phone:
949-975-8588
Document Type:
Master Specification
Scope:
Firestopping and smoke seals in walls, floors, and joints
Standards Referenced:
ASTM E84, ASTM E119, ASTM E814, UL1479
Units:
Metric and Imperial
Target Audience:
Designers and construction professionals
Notes:
Includes optional text and SPEC NOTES for guidance, to be adapted per project
Year:
2024
Region / City:
Washington State, USA
Subject:
Wildfire Smoke Safety Regulations for Agricultural Workers
Document Type:
Safety Plan Template
Organization:
Employer (Agricultural Workplace)
Author:
Not specified
Target Audience:
Employers in agriculture, employees working outdoors
Effective Date:
January 15, 2024
Date of Approval:
Not specified
Date of Changes:
Not specified
Year:
2023
Region / City:
Boise, ID
Topic:
Smoke and Draft Control
Document Type:
Technical Specification
Organization / Institution:
Smoke Guard, A CSW Industrials Company
Author:
Not specified
Target Audience:
Contractors, Architects, Engineers
Period of Validity:
Not specified
Approval Date:
Not specified
Revision Date:
Not specified
Year:
2023
Region / City:
USA
Subject:
Workplace safety, Wildfire smoke protection, Respiratory protection
Document Type:
Policy
Organization:
[Company Name]
Author:
[Author’s Name]
Target Audience:
Outdoor workers, Supervisors, Employers
Period of Application:
Indefinite
Approval Date:
[Date of approval]
Modification Date:
[Date of modification]
Document type:
Community information fact sheet
Status:
Official
Issuing authority:
Victorian Government
Department:
Department of Health
Place of publication:
Melbourne, Victoria, Australia
Publisher address:
1 Treasury Place, Melbourne
Copyright holder:
State of Victoria, Australia
Publication date:
January 2026
Subject:
Bushfire smoke and public health
Target audience:
General public, including sensitive groups
Related organisations:
VicEmergency; Environment Protection Authority (EPA) Victoria; Asthma Foundation of Victoria; NURSE-ON-CALL
Year:
2026
Location:
Hines VA Campus, Building 215, United States
Document Type:
Performance Work Statement (PWS)
Organization:
Department of Veterans Affairs, Office of Information & Technology, IT Operations and Services
Audience:
Contractors
Scope:
Replacement of approximately 14,800 sq. ft. of acoustical ceiling tiles and removal of 12 ceiling-mounted air purifiers in the data center
Standards Compliance:
NFPA codes, ASTM C635 & ASTM C636
Tasks:
Ceiling tile removal and installation, device disconnect/reconnect, dust control, grid repair, high bay access, return grill installation
Safety Requirements:
Protect computer equipment during construction, use HEPA filter vacuums, maintain active sprinkler and fire alarm systems
Year:
2024
Region / City:
Morgantown, PA
Theme:
BBQ Competition
Document Type:
Application Form
Organ / Institution:
Twin Valley Fire Department
Author:
Tom Hornberger
Target Audience:
KCBS Members, BBQ Competitors
Period of Validity:
May 17-19, 2024
Date of Approval:
Not specified
Date of Changes:
Not specified
Year:
2025
Location:
Morgantown, PA, USA
Event Type:
BBQ Competition
Organizer:
Twin Valley Fire Department
Sanctioning Body:
KCBS
Categories:
Beef Brisket, Pork Ribs, Chicken, Pork
Entry Fee:
$300–$550 depending on days
Setup Time:
May 16, 2025, from 7 AM
Judging Dates:
May 17–18, 2025 at 12:00 PM
Awards Presentation:
May 17–18, 2025 at 4:00 PM
Participant Requirements:
Chief Cook signature, payment method, electrical and water provisions
Date:
August 27, 2025
Region / City:
Toronto, Ontario, Canada
Issuing Authority:
Environment & Climate Change Canada; Ontario Ministry of Environment, Conservation and Parks
Target Audience:
Child Care and BASP staff, school Principals, parents of young children
Type of Document:
Advisory / Public Health Notice
Risk Factors:
Infants, young children, people with chronic health conditions, individuals engaging in strenuous outdoor exercise
Air Quality Tool:
Air Quality Health Index (AQHI)
Recommendations:
Outdoor activity guidance based on AQHI levels, use of HEPA filters, minimizing indoor air infiltration
Contact:
Child Care Services, Early Years, Toronto District School Board, Tel: 416-394-7965, [email protected]
Public Health Guidance Period:
Day of advisory and subsequent occurrences as needed
Year:
2015
Region / City:
Minneapolis, MN
Topic:
HVAC, Smoke Control
Document Type:
Technical Specification
Organization / Institution:
Twin City Fan & Blower, Twin City Fan Companies, Ltd.
Author:
Not specified
Target Audience:
Engineers, Contractors, HVAC Professionals
Effective Period:
Not specified
Approval Date:
Not specified
Amendment Date:
Not specified
Application:
Smoke and Heat Removal Fans for HVAC
Fan Size:
24 to 60 inches (610 mm to 1,525 mm)
Airflow:
4,000 to 82,600 CFM (6,796 to 140,336 m³/hour)
Static Pressure:
Up to 1.5 inches wg (373 Pa)
Warranty Period:
12 months from startup or 18 months from shipment, whichever first occurs
Manufacturer:
Twin City Fan & Blower, Minneapolis MN
ISO Certification:
ISO 9001
Relevant Standards:
AMCA, NEMA, UL/cUL, NFPA
Description:
Guide specification for belt-driven tubeaxial fans used in smoke and heat control systems for fire safety in buildings, including performance requirements, installation, and warranty details.
Year:
2022
Region / City:
N/A
Topic:
Fire & Smoke Damper Testing
Document Type:
Training Aid
Organization:
National Energy Management Institute Committee
Target Audience:
Contractors, Supervisors, Technicians, FLS Supervisors
Period of Validity:
N/A
Approval Date:
N/A
Modification Date:
N/A
Applicable Standards:
NFPA 80 – 2022, NFPA 105 – 2012, NFPA 92 – 2018
Inspection Frequency:
Periodic
Document Purpose:
Guide for developing inspection methods and procedures for FLS dampers